NFS 320 Addressable Fire Alarm Control Panel

The NFS-320 intelligent Fire Alarm Control Panel is part of the ONYX® Series of Fire Alarm Controls from NOTIFIER. In stand-alone or network configurations, ONYX Series products meet virtually every application requirement. Designed with modularity and ease of system planning, the NFS-320 can be configured with just a few devices for small building applications, or for a large campus or high-rise application. Simply add additional peripheral equipment to suit the application. For installations using NFS-320C, an optional ACM Series annunciator can be mounted in the same cabinet (up to 48 zones/points, order seperately).

|
Specifications |
• Primary input power, CPU-320 board: 120 VAC,
50/60 Hz, 3.0 A. CPU-320E board: 220/240 VAC,
50/60 Hz, 1.5 A. |
• Total output 24 V power: 6.0 A in alarm. NOTE:
The power supply has a total of 6.0 A of
available power. |
|
This is shared by all internal circuits. |
|
• Standard notification circuits (4): 1.5 A each. |
|
• Resettable regulated 24V power: 1.25 A. |
• Two non-resettable regulated 24V power outputs:
– 1.25 A
– 0.50 A. |
|
• Non-resettable 5V power: 0.15 A. |
• Battery charger range: 18 AH – 200 AH. Use separate
cabinet for batteries over 25 AH. |
|
• Float rate: 27.6 V. |
|
|
Cabinet Specifications |
• NFS-320 cabinet dimensions: Backbox: 18.12 in.
(46.025 cm) width; 18.12 in. (46.025 cm) height;
5.81 in. (14.76 cm) depth. |
• Door: 18.187 in. (46.195 cm) width; 18.40 in.
(46.736 cm) height; 0.75 in. (1.905 cm) depth. |
|
• Trim ring: Molding width is 0.905 in. (2.299 cm). |
|
Agency Listings and Approvals |
The listings and approvals below apply to the basic
NFS-320 control panel. In some cases, certain modules
may not be listed by certain approval agencies, or
listing may be in process. Consult factory for latest
listing status. |
|
• UL Listed: file S635 |
• ULC Listed: file S635
(NFS-320C only, Excludes IPDACT) |
|
• CSFM: 7170-0028:244; 7165-0028:243 |
|
• FM Approved |
|
• MEA: 128-07-E , FDNY Certificate #6007, #6025 |
|
• FDNY COA # 6022 (HS-NCM) |
|
This information is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.